I am working on a restoration of a small 1870s train station constructed of serpentine stone in the Philadelphia, PA, area. In many areas the stone has deteriorated, leaving deep “divets” in the exterior wall faces and, in some cases, there is no stone at all. Our intent is to build (infill) the walls back to a flush face for stucco treatment for the lower portions of the wall and to repair or replace stone above that point. Is there a minimum amount of treatment recommended for a shotcrete application? If it can be used for such an application, is reinforcement required? The stone is rather friable and I don’t want to attach too much to it for fear of further damaging the stone.

This is a great application for shotcrete placement of high-quality concrete without formwork. If you are merely adding shotcrete to fill out to a uniform surface profile without any structural requirements you may not need reinforcement. However, it may still be advisable to include fibers in the shotcrete mixture to help control plastic shrinkage cracking. Generally, you would want to keep a minimum thickness of 1 in. (25 mm) to provide enough thickness for finishing. If you need the shotcreted sections to be self-supporting and carry loads as structural concrete, you should consult with a structural engineer to determine the appropriate thickness and reinforcement for the expected loads. Shotcrete is a placement method for concrete, so standard reinforced concrete design is appropriate for shotcreted sections.

How much shotcrete coverage over No. 4 reinforcing bar is required?

Shotcrete is simply a placement method for concrete. The specified concrete cover over reinforcing bar is usually included in contract documents for construction and values vary depending on exposure conditions. ACI 318 provides cover requirements for structural concrete in buildings, and ACI 350 provides cover requirements for concrete liquid-containing structures. Local building codes and fire codes may also require specific cover in concrete construction. If your project doesn’t specify the cover requirements, we recommend you consult with a professional engineer experienced in the type of project you are working on to learn what the code requirements may be.

What is the best way to check the sand-to-cement ratio in gunite batch trucks? Is it normal (common) to get up to 10% air straight from the mixing auger? I had a gunite truck fill a 5 gal. (19 L) bucket with mixed material (sand and cement) then put it in my lab mixer and wetted it up to a 3 in. (75 mm) slump and ran a test for air, unit weight, and cast a set of cylinders. I am trying to figure out the sand-to-cement ratio, but I don’t have a cement diverter to run a real-time sand-to-cement ratio test, so I am testing dispensed material to see if it makes 70% strength in 7 days, which indicates a good mixture. Are there any other ways of checking sand-to-cement proportions? I tested the mixed material in a lab about 5 minutes after it was dispensed.

By “gunite batch truck” we assume you are referring to a volumetric mixer supplying material for a dry-mix shotcrete operation. Gunite is the original tradename for what we now call dry-mix shotcrete. Here’s the description from an ACI Materials Journal (January-February 1991 issue) article about the calibration of volumetric mixers:

“To insure production of quality concrete, each volumetric-measuring unit must be calibrated for each respective concrete ingredient, following the manufacturer’s recommendations and ASTM C 685. These ingredients must be the same as those to be used in actual concrete production. The measuring devices for aggregates, cement, and dry admixtures are calibrated by weighing the discharged ingredient. Devices for water, latex modifier (if required), and liquid admixtures such as air-entraining and water-reducing admixtures generally are calibrated by weighing or measuring the volume of the discharged ingredient. The objective of calibration is to coordinate the discharge of all concrete ingredients to produce the proper mixture.”

ASTM C685/C685M states, “The proportioning and indicating devices shall be individually checked by following the equipment manufacturer’s recommendations as related to each individual concrete batching and mixing unit. Adequate standard volume measures, scales, and weights shall be made available for the checking accuracy of the proportioning mechanism.” Thus, you need to check with your equipment supplier for their recommended procedures to verify batching. Because concrete mixtures always are based on weight of ingredients there you will need to weigh a given volume to confirm the batching is accurate.

The air content test is a measure of total air so includes both entrapped and entrained air. Ten percent is definitely high. The 10% air is likely not representative of the in-place shotcrete. It may have been an issue with the lab mixer introducing more entrapped air for some reason. Estimating the air content from the unit weight test requires a good value for the theoretical unit weight. I’m not sure if you have that with the volumetric batching. You should run the air meter test (ASTM C231/C231M) to measure the air content to get a more accurate assessment.

Regarding the verification of mixture proportions, this is from ASTM C685/C685M:

“7.5 Proportioning Check—Whenever the sources or characteristics of the ingredients are changed, or the characteristics of the mixture are noted to have changed, the purchaser is permitted to require a check of the fine aggregate content and the coarse aggregate content by use of the washout test. Essentially, in the washout test, 1 ft3 [0.03 m3] of concrete is washed through a No. 4 [4.75-mm] sieve and through a No. 100 [150-µm] sieve; that retained on the No. 4 sieve is normally considered coarse aggregate whereas that passing the No. 4 and retained on the No. 100 sieve is considered fine aggregate. Corrections to the quantity of aggregates (per cubic foot or cubic meter of concrete) shall be made if the original sieve analysis of each aggregate is available.”

Because you are only interested in the sand and cement, you can simply weigh the sample of concrete, then wash out all the cement, and then weigh the remaining sand. You would need to bring the sand to roughly the same moisture content as the sand in the truck, so you aren’t including in the weight of excess water in the sand. You should note that with shotcrete impact during placement we will generally lose 50% of the air content, so your final in-place air should be around 5%. That is a reasonable value for good freezing-and-thawing durability.

I would like to better understand the limitations related to the height of install when it comes to the gunite application. Because gunite is a dry concrete mixed with water at the nozzle of the applying apparatus, I have been told by others in the industry that the application is only intended for use of walls less than 4 or 5 ft tall. If that is the case, is it safe to assume that the gunite application strategy should not be used for below-grade vaults exceeding a height of 5 ft? I am looking for design literature specific to gunite.

Dry-mix shotcrete adds mixing water to the dry concrete materials as the concrete materials flow through and out the nozzle. Gunite is the original tradename for dry-mix shotcrete. Though you may not find design information using the old gunite name, you will find numerous current design references to dry-mix shotcrete. This includes ACI 506R-16, “Guide to Shotcrete”; ACI 506.2-13, “Specification for Shotcrete”; ACI 506.6T-17, “Visual Shotcrete Core Quality Evaluation Technote”; ACI 372, “Design and Construction of Circular Wrapped Prestressed Concrete Tanks”; ACI 350-06, “Code Requirements for Environmental Engineering Concrete Structures”; ACI 350.5, “Specifications for Environmental Concrete Structures”; and seven ASTMs that directly cover shotcrete. ACI 318-19, “Building Code Requirements for Structural Concrete,” has also added specific shotcrete provisions. Dry-mix shotcrete has been used for decades to build structural concrete walls over 50 ft high in circular prestressed concrete tanks that withstand a full head of water pressure. This is a substantially greater water pressure than your 5 ft vault wall would experience. There are no limitations in the dry-mix placement process that would preclude use in high walls. Both dry-mix and wet-mix shotcrete using quality materials, proper equipment, and experienced placement crews will produce in-place concrete of equal strength, durability, and low permeability. However, generally wet-mix shotcrete can offer placement rates up to four times higher than dry-mix. Thus, in thicker, longer walls, wet-mix shotcrete may be more cost-effective because it can be placed faster.

One quick question regarding the “grading” of cores based on 506.2: I imagine the 1995 standard-based 1 through 5 grading system is no longer valid? In one case the special inspector has failed a core (score of 5) simply because a piece of it broke off during the coring and removal from the coring cylinder. I’m leery of that type of failed rating. What do you think about that, and core grading in general?

The current version of the ACI “Specification for Shotcrete” is ACI 506.2-13 and purposely eliminated the core grading due to many problems that arose in the field in trying to equitably apply the procedure. ACI 506 has a new document ACI 506.6T-17, “Visual Shotcrete Core Quality Evaluation Technote,” that is intended to assist specifiers with evaluating shotcrete core quality for an intended use. So yes, the 506.2-95 version of the specification and the grading system it included is no longer supported as an industry standard.

Regarding grading, a shotcrete score of 5 under the deprecated grading system just because the core broke during coring is unreasonable. The coring operation exerts a massive force on the core, as it basically rips it out of the concrete. We have seen many instances where the core snapped where a large reinforcing bar horizontally crossed the core and effectively created a slip plane that reduced the shear resistance of the core section to the torque created by the coring. In those cases, examining the core hole for any evidence of shotcrete problems would be appropriate and then discounting the core itself.

In summary, my position and the ACI 506 Committee’s position is that core grading should not be used for evaluating shotcrete quality. The ACI 506.6T-17 Technote document should be the current reference for making a reasonable evaluation of shotcrete quality for the intended use.

What is the minimum spacing between reinforcing bar recommended in a shotcrete swimming pool deep-end wall. The engineer is calling out for 12 in. (300 mm) walls with a double mat of No. 5 bars at 4 in. (100 mm) on center each way. In my opinion, this does not give enough space to properly encase the reinforcing bar with shotcrete without creating voids and trapping uncontrollable rebound.

The engineer designs the wall based on the loads anticipated on it throughout its service life. The minimum spacing for noncontact lap splices as indicated in ACI 506.2, “Specification for Shotcrete,” is:

“Clearance of at least three times the diameter of the largest reinforcing bar; three times the maximum size aggregate; or 2 in., whichever is least”

In your case with No. 5 bars, the 2 in. (50 mm) minimum probably controls and would then provide a 2.6 in. (64 mm) center-to-center spacing. No. 5 bars at 4 in. spacing can be shot properly with proper materials and technique. An ACI-certified shotcrete nozzleman will have had education that explains how this configuration or even closer spacing can be shot properly. Experienced shotcrete contractors doing structural concrete walls do this type of work routinely with excellent results. If you are concerned about encasement of the reinforcing steel in the back curtain of steel you may consider erecting only the back curtain of steel, shooting the wall out to the location of the outer curtain of reinforcement, erecting the outer curtain, and then shooting out to the final surface. Experienced shotcrete contractors have shot in thick sections (36 in. [900 mm] thick or more) with heavy reinforcement (No. 11 at 4 in.) using this technique.

What is the cure time for shotcrete before paint can be sprayed? And what type of paint (latex or oil-based) would work best?

Shotcrete is a placement method for concrete. Thus, cure time is the same as what the coating manufacturer recommends for new concrete surfaces. Because moisture in the concrete surface is part of the concern of bond from manufacturers, a water-based latex may be preferable to oil-based, but you should discuss the appropriate time and materials with your coating supplier.

With structural shotcrete walls, what is the anticipated shear strength of the sprayed shotcrete to a vertical wall with geotextile fabric applied to a retention system? What is the anticipated dead load of the sprayed shotcrete at the base of the sprayed wall when the shotcrete wall is sprayed to a nominal thickness of 6 in. (150 mm)? Also, what is the maximum wall thickness that can be sprayed in a single pass application with a normal mixture design to achieve 4800 to 5000 psi strength?

Shotcrete is a placement method for concrete. Thus, structural properties are equivalent to those of concrete with specified strength. Shotcrete compressive strengths will normally range from 4000 to 7000 psi at 28 days, so your 4800 to 5000 psi (33 to 35 MPa) is very normal. Density of shotcrete placed concrete is the same as cast concrete ranging from 145 to 150 lb/ft3. Walls can generally be built at any required thickness because we will create the wall by bench shooting building the wall from the bottom to the top in vertical lifts.

We are applying a new shotcrete shell to an existing building. We are calling for a 5 in. (125 mm) base coat with a 1/4 in. (6 mm) brush-finished flash coat. We are specifying a color admixture for all of the shotcrete. It is a large building and we anticipate several days of shotcrete operations. Would it be wise to allow (or even specify): 1) the color admixture to be used in the flash coat only? 2) all of the flash coat to be applied at once, possibly days after all of the base coat has been installed, to achieve a more uniform final appearance?

If you only need color in the exposed shotcrete surface, just putting color in the flash coat should be adequate as long as the flash coat is continuous across the entire area. You may want to specify the final “flash” layer to be thicker, perhaps 1/2 in. (12 mm) to 1 in. (25 mm) thick. This would help assure consistent color and still allow the finishers to produce a consistent final texture. As long as the concrete materials are the same in the production, you wouldn’t need to shoot the final layer all in one day. Also, be sure curing methods are the same for the entire area as varying moisture can sometimes affect the early appearance of the coloring, though it usually balances out over time.

I am currently researching shotcrete machines for a sewerage channel. Would dry-process or wet-process be more functional and efficient? I am new to the industry, so could you please give me some background information regarding the equipment used as well as information about the techniques and processes you would use? Could you also inform me about the factors like humidity and what effect they would have on what process you would use and how you would apply it? Please also let me know about any other information that you would consider as having a significant effect on the overall process.

The thickness of the shotcrete placement, site logistics, and the availability of ready-mixed concrete, as well as expertise of the shotcrete contractor would likely determine the most cost-effective method for shotcrete placement. Both dry-mix and wet-mix will produce structural concrete in place with similar physical properties and durability. Wet-mix can generally produce more volume of material placed per hour than dry-mix. You had several basic questions about shotcrete that can be answered by visiting sections of Shotcrete.org. On our website, you will find the informational pages shotcrete.org/Resources and shotcrete.org/ArchiveSearch beneficial. The Resources page lists many shotcrete-specific articles and web resources. The Archive Search allows you to search through our Shotcrete magazine archive for past articles using keywords. You may also find ACI 506R-16, “Guide to Shotcrete,” an informative primer on all aspects of shotcrete. You can purchase a PDF copy of the Guide from ACI at www.concrete.org/store/productdetail.aspx?ItemID=50616. ACI Committee 506, Shotcreting, also has several other technical documents available for specification for shotcrete, evaluation of shotcrete cores, specifying underground shotcrete, and fiber-reinforced shotcrete you can find on the ACI website.