We have a cast-in-place wall with extensive rock pockets and voids from inadequate vibration during casting. One option is to tear down the wall and replace, however we are wondering if shotcrete can be used to repair the deficiencies. If so, what are the recommended procedures to prepare and shotcrete the repairs?

Shotcrete is a great solution to your wall casting issue. In all shotcrete repair to get the best bond you need to:
1. Chip back to sound substrate – all the rock pockets and voids should be chipped out (or you can use hydrodemolition) to sound concrete.
2. If the chipped-out area is deep into the wall, make sure to have the opening at about a 45° angle from the back of the chipped out area to the surface so that the air flow providing shotcrete’s high velocity can escape and not be trapped.
3. Do not feather edge the perimeter of the repaired opening. Provide a ¾ to 1 in. (19 to 25 mm) roughly square shoulder at the perimeter edge. If this is sawcut make sure the sawed surface is roughened before shotcreting.
4. Thoroughly clean the chipped-out area to remove all dust.
5. Bring the entire chipped out area to a saturated surface dry condition.
6. Do NOT use a bonding agent. It will detract from the inherent excellent bond of shotcrete.
7. Use an experienced shotcrete nozzleman (ACI-certified in the vertical orientation for the process being used) with a quality concrete mixture, and proper shotcrete equipment.
8. Make sure the shotcrete finishers are experienced and do not tear or delaminate the shot sections.
9. Protect the freshly shot and finished sections from freezing or extremely hot weather.
10. Cure the shot sections for a minimum of 7 days. A water cure is preferred to a curing membrane. Either wet-mix or dry-mix would be suitable for your project.

The shotcrete contractor you select for the project should recommend the process they are best suited for based on their crew experience and equipment. Appropriate testing for this type of repair may include compression testing of the materials from shotcreted panels (ASTM C1140 Standard Practice for Preparing and Testing Specimens from Shotcrete Test Panels, ASTM C1604 Standard Test Method for Obtaining and Testing Drilled Cores of Shotcrete, and ACI 506.2 Specification for Shotcrete), and bond pull-off tests to verify the bond of the shotcreted material to the original substrate. For more guidance on shotcrete and its use in concrete repairs, you may want to review ACI 506R-16 Guide to Shotcrete, as it can give you more detailed information about shotcrete materials, surface preparation, shotcrete crews and placement, testing, protection and curing.

Can a gunite bridge surface be painted? And if so, what preparation/materials are recommended.

Yes, shotcrete is a placement method for concrete, so any coating appropriate for concrete would be applicable specify new concrete should be a certain age before applying their coating. Generally, the concrete surface should be clean and dry before coating. The surface texture provided on the shotcrete can affect the coating application. A hard, smooth steel trowel finish will tend to be quite slick, and the coating may not bond as well as a floated or sponge finish. A light abrasive blast may be considered to roughen the surface and give more bond. If using a gun or rodded finish for the shotcrete, the coating will generally require quite a bit more material to be able to fill the depressions in the surface.

Repairs and Strengthening of Brick Arch Masonry Storm Water Drains for MCGM

The storm water drains in the city of Mumbai, India, are over 100 years old and constructed with brick arch masonry during the British Era (Fig. 1). The storm water drains (SWD) were prone to frequent cave-ins. To prevent cave-ins, enhance their safety, and maintain the SWD system, the Municipal Corporation of Greater Mumbai (MCGM), under the Central Government of India “BRIMSTOWAD” Scheme, initiated a detailed survey and mapping of the SWD for the City of Mumbai.

I am working on a fire re-build project near Napa, CA. The existing building has 12 in. (300 mm) thick shotcrete basement walls. There are many areas where the concrete cover spalled off from the rebar. The rebar appears to be ingood condition with no visible buckling. Is it possible to repair these walls with a 1 1/2 to 2 in. (38 to 50 mm) layer of shotcrete to restore the concrete cover? If so, what sort of surface prep is required? Is a concrete bonding agent required?

Yes, this is definitely a good application for shotcrete. To restore the cover:

  • Chip or hydrodemo back to sound concrete. If a reinforcing bar is more than half exposed, chip at least 1 in. (25 mm) back behind the bar.
  • Make sure the surface is roughened and clean.
  • Bring the concrete surface to saturated surface dry (SSD) condition. This means the surface feels damp but water is not picked up on a hand.
  • Make sure the shotcrete placement is properly executed. Use of an ACI-certified shotcrete nozzleman is recommended.
  • No bonding agent should be used. It will interfere with the natural bonding characteristics of shotcrete placement.
  • If chipping out a section do not feather edge. Provide a ¾ to 1 in. (19 to 25 mm)) depth of cut at the edge to provide adequate thickness for the integrity of the shotcreted material at the edge.

 

This article on the excellent bond between shotcrete provides more detail: https://shotcrete.org/wp-content/uploads/2020/05/2014Spr_TechnicalTip.pdf

 

Outstanding Rehabilitation & Repair Project

Project Name:
10th Ave SE Bridge Rehab

Location:
Minneapolis, MN

Shotcrete Contractor:
PCiRoads, LLC

Architect/Engineer:
The LiRo Group

Material Supplier/Manufacturer:
TCC Materials & King Packaged Materials

Equipment Manufacturer:
Gary Carlson Equipment / Putzmeister Allentown

General Contractor:
Lunda Construction Co.

Project Owner:
City of Minneapolis

Honorable Mention Project

Project Name:
Surface Reef Silo 4

Location:
North-West Province, South Africa

Shotcrete Contractor:
Shotcrete Africa SCP

Architect/Engineer:
Royal Bafokeng Platinum

Material Supplier/Manufacturer:
FSE Engineering Services

Equipment Manufacturer:
Amsteele Systems

General Contractor:
Shotcrete Africa SCP

We are working on a repair/renovation project in Boston. A long-concealed wall next to an adjacent property is now visible as the adjacent property is being renovated. We have been told that our wall must have a 2-hour fire rating. Our wall is composed of CMU masonry and exposed structural steel members. Applying shotcrete to the CMU and steel is a good solution for several reasons. Would you provide shotcrete specifications that will have a 2-hour fire rating on CMU and structural steel?

Shotcrete is a placement method for concrete. Thus, the fire resistance for shotcrete placement is the same as concrete. The primary reference for fire resistance of concrete is ACI 216.1-14(19) Code Requirements for Determining Fire Resistance of Concrete and Masonry Construction Assemblies. 

Shotcrete Incorporated into ACI 318-19 Building Code

Since the shotcrete process originated well over 100 years ago, improvements in materials, equipment, and placement techniques have enabled it to become a well-proven method for structural concrete placement. The efficiency and flexibility of shotcrete have been used to great advantage in sizable structural projects, as the high-velocity impact inherent in the process provides the compaction needed to turn low-slump concrete into freestanding vertical and overhead placements with minimal formwork.

Duck Island Wastewater Treatment Plant- Screw Pump Rehabilitation

The Duck Island Clean Water Facility, located in Lowell, MA, is a 32 million gal./day (120 megaliter/day) activated sludge treatment plant. The facility accepts wastewater from several Massachusetts cities and towns, including the City of Lowell and the towns of Chelmsford, Dracut, Tewksbury, and Tyngsborough. The service area includes approximately 220,000 people. The facility has been in the news for the past decade due to its need for massive repairs

Falls Village Penstock #1 Structural Shotcrete Rehabilitation Project

In early November of 2018, Knowles Industrial Services Corporation (KISC) was issued a contract by First Light Power Resources, Inc. (FLP) to perform a structural shotcrete liner within a steel-riveted penstock at the Falls Village Hydro Electric Plant in Canaan, CT. FLP’s request for bids permitted contractors to provide a design-build approach for a structurally self-sustaining system to be built within the penstock interior. The existing 9 ft (2.7 m) diameter, 360 ft (110 m) long penstock was buried in its entire length on a steep bank and crossed underneath a live highway. Penstock replacement by excavation proved to be too costly, as much of the existing penstock beneath the roadway was encased in reinforced concrete requiring significant demolition and interruption to traffic in this area.