RepairQ We are working on a repair/renovation project in Boston. A long-concealed wall next to an adjacent property is now visible as the adjacent property is being renovated. We have been told that our wall must have a 2-hour fire rating. Our wall is composed of CMU masonry and exposed structural steel members. Applying shotcrete to the CMU and steel is a good solution for several reasons. Would you provide shotcrete specifications that will have a 2-hour fire rating on CMU and structural steel?
Shotcrete is a placement method for concrete. Thus, the fire resistance for shotcrete placement is the same as concrete. The primary reference for fire resistance of concrete is ACI 216.1-14(19) Code Requirements for Determining Fire Resistance of Concrete and Masonry Construction Assemblies.